40
A
Setting an indoor unit address and
installation option (Cont.)
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
05
Use of Auto Change Over
for HR only in Auto mode
(When setting SEG3)
Standard heating temp.
Oset
(When setting SEG3)
Standard cooling temp.
Oset
(When setting SEG3)
Standard for mode change
HeatingCooling
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1
(When setting SEG3)
Standard for mode change
CoolingHeating
(When setting SEG3)
Time required for mode
change
Compensation option for
Long pipe or height
dierence between
indoor units
--
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2- - - -
Control variables when using
hot water / external heater
SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
3- - - - -
Q
05 series installation option
*
Advanced function: Controlling cooling/heating current or power saving with motion detect.
(*1) Minimizing fan operation when thermostat is o
- Fan operates for 20 seconds at an interval of 5 minutes in heat mode.
(*2) 1: Fan is turned on continually when the hot water heater is turned on,
3: Fan is turned o when the hot water heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option,install the Mode Select switch(MCM-C200) on the outdoor unit and x it as cool mode.
(*3) When the following 2 or 3 is used as external heater On/O signal, the signal for monitoring external contact control will not be output.
2: Fan is turned on continually when the external heater is turned on,
3: Fan is turned o when the external heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option,install the Mode Select switch(MCM-C200) on the outdoor unit and x it as cool mode.
g If Fan is set to o for cooling only indoor unit by setting the SEG9=3 or SEG15=3, you need to use an external sensor or wired remote
controller sensor to detect indoor temperature exactly.
(*4) Default setting value
- 4Way Cassette, Mini 4Way Cassette: 9 °F(5 °C)
- Other indoor units: 3.6 °F(2 °C )
Air Flow
Suction side Discharge side
Electronic heater should
not be installed.
t Do not install the electronic heater in the ow channel of the indoor unit fan.
Duct Indoor unit
Caution