41
ENGLISH
Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation
PAGE MODE
Use of Auto Change
Over for HR only in
Auto mode
(When setting SEG3)
Standard heating
temp. Oset
(When setting SEG3)
Standard cooling temp.
Oset
(When setting SEG3)
Standard for mode
change
Heating
→
Cooling
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
05
0
Follow
product
option
0 0°F(0°C) 0 0°F(0°C) 0 1.8°F(1°C)
1
Use Auto
Change
Over for
HR only
1 0.9°F(0.5°C) 1 0.9°F(0.5°C) 1 2.7°F(1.5°C)
2 1.8°F(1°C) 2 1.8°F(1°C) 2 3.6°F(2°C)
3 2.7°F(1.5°C) 3 2.7°F(1.5°C) 3 4.5°F(2.5°C)
4 3.6°F(2°C) 4 3.6°F(2°C) 4 5.4°F(3°C)
5 4.5°F(2.5°C) 5 4.5°F(2.5°C) 5 6.3°F(3.5°C)
6 5.4°F(3°C) 6 5.4°F(3°C) 6 7.2°F(4°C)
7 6.3°F(3.5°C) 7 6.3°F(3.5°C) 7 8.1°F(4.5°C)
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation
PAG E
(When setting SEG3)
Standard for mode
changing Cooling
→
Heating mode
(When setting SEG3)
Time required for
mode change
Compensation option
for Long pipe or height
diference between
indoor units
Indication
and Details
Indication Details Indication Details Indication Details Indication Details
1
0 1.8°F(1°C) 0 5 min. 0
Use default
value
1 2.7°F(1.5°C) 1 7 min.
1
1) Height
difference
1)
is
more than 30m
( 98.4ft) or
2) Distance
2)
is longer than
110m(360.9ft)
2 3.6°F(2°C) 2 9 min.
3 4.5°F(2.5°C) 3 11 min.
4 5.4°F(3°C) 4 13 min.
2
1) Height
difference
1)
is
15~30m( 49.2ft
~ 98.4ft )or
2) Distance
2)
is
50~110m
(164.04ft~
360.9ft)
5 6.3°F(3.5°C) 5 15 min.
6 7.2°F(4°C) 6 20 min.
7 8.1°F(4.5°C) 7 30 min.
Q
05 series installation option(Detailed)