Electrical wiring work
Specification of the circuit breaker and power cable
Standard single (Heat Pump)
Model MCA MFA
AM080JXVAFH 28.0 40
AM100JXVAFH 34.0 50
AM120JXVAFH 36.0 50
AM140JXVAFH 50.0 63
AM160JXVAFH 56.1 63
AM180JXVAFH 66.5 75
AM200JXVAFH 73.0 80
AM220JXVAFH 70.0 80
AM240JXVAFH 70.0 80
AM260JXVAFH 73.0 80
❋ When installing outdoor units in module, select the power supply cable according to the sum of outdoor unit capacity.
(Refer to the table for each model.)
❋ Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible
cord. (Code designation IEC: 60245 IEC 66 / CENELEC: H07RN-F)
Standard single (Heat Pump)
Model MCA MFA
AM080JXVAJH/AZ 17.4 25
AM100JXVAJH/AZ 18.9 25
AM120JXVAJH/AZ 20.6 32
AM140JXVAJH/AZ 25.0 32
AM160JXVAJH/AZ 28.1 40
AM180JXVAJH/AZ 33.8 50
AM200JXVAJH/AZ 41.8 63
AM220JXAVJH/AZ 46.0 63
❋ When installing outdoor units in module, select the power supply cable according to the sum of outdoor unit capacity.
(Refer to the table for each model.)
❋ Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible
cord. (Code designation IEC: 60245 IEC 66 / CENELEC: H07RN-F)