43
Size of the pipe between branch joints (B)
Select the pipe size according to the sum of indoor unit capacity which will be connected after the branch.
However, if the size of the pipe between branch joints (B) is bigger than the size of the pipe connected to the
outdoor unit (A), apply the pipe size (A).
Indoor unit capacity (kW)
Pipe size (mm)
Liquid pipe Low pressure gas pipe High pressure gas pipe
15.0kW and below
Ø 9.52
Ø 15.88
Ø 15.88
Over 15.0kW ~ 22.4kW and below Ø 19.05
Over 22.4kW ~ 28.1kW and below Ø 22.22
Ø 19.05
Over 28.1kW ~ 33.6kW and below
Ø 12.70
Ø 28.58
Over 33.6kW ~ 45.0kW and below
Ø 22.22
Over 45.0kW ~ 50.4kW and below
Ø 15.88Over 50.4kW ~ 63.3kW and below
Ø 28.58
Over 63.3kW ~ 70.3kW and below
Ø 34.92
Over 70.3kW ~ 98.4kW and below
Ø 19.05
Over 98.4kW ~ 105.5kW and below
Ø 41.28Over 105.5kW ~ 135.2kW and below
Ø 34.92
Over 135.2kW ~ 169.0kW and below
Over 169.0kW Ø 22.22 Ø 53.98 Ø 41.28
Size of the pipe between the branch joint and the indoor unit
Make a selection according to outdoor unit capacity.
Indoor unit capacity (kW)
Pipe size (O.D. mm)
Liquid pipe Gas pipe
6.0kW and below Ø 6.35 Ø 12.70
7.2kW ~ 16.0kW and below Ø 9.52 Ø 15.88
20kW ~ 23.0kW and below Ø 9.52 Ø 19.05
Over 23.0kW Ø 9.52 Ø 22.22
DVM S HE_IM_DB68-05461A-08_EN.indd 43 2017-03-24 오후 1:38:20