Refrigerant pipe installation
(A)
(B)
33.6kW 39.2kW
(D)
(E)
(F)
(C)
(3)
(2)
(1)
44.8kW
Branch joint
Branch joint between outdoor units (C)
Classication Model name Specication (kW)
Liquid/Low pressure Y-joint (C)
MXJ-TA3419M 135.2kW and below
MXJ-TA4122M Over 140.2kW
High pressure Y-joint (C)
MXJ-TA3100M 135.2kW and below
MXJ-TA3800M Over 140.2kW
First branch joint (D)
Make a selection according to outdoor unit capacity.
Classication Outdoor unit capacity (kW) Model name of the branch joint
Liquid/Low pressure Y-joint (C)
40.0kW and below MXJ-YA2512M
45.0kW MXJ-YA2812M
50.4kW ~ 67.2kW MXJ-YA2815M
73.6kW ~ 95.2kW MXJ-YA3419M
101.6kW ~ 135.2kW MXJ-YA4119M
140.2kW and over MXJ-YA4422M
High pressure Y-joint (C)
22.4kW MXJ-YA1500M
28.0kW ~ 67.2kW MXJ-YA2500M
73.6kW ~ 135.2kW MXJ-YA3100M
140.2kW and over MXJ-YA3800M
DVM S HE_IM_DB68-05461A-08_EN.indd 44 2017-03-24 오후 1:38:20