Installation Procedure
Installation Procedure
05 series installation option (Detailed)
Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation PAGE MODE
Use of Auto Change Over
for HR only in Auto mode /
Use of Cooling only indoor
unit of HR
(When setting SEG3)
Standard heating temp.
Offset
(When setting SEG3)
Standard cooling temp.
Offset
(When setting SEG3)
Standard for mode change
²ʪɇϩ˝Aͱͱ˝
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
05
0
Follow
product
option
0 0 °C 0 0 °C 0 1 °C
1 0.5 °C 1 0.5 °C 1 1.5 °C
1
Use Auto
Change Over
for HR only
2 1 °C 2 1 °C 2 2 °C
3 1.5 °C 3 1.5 °C 3 2.5 °C
4 2 °C 4 2 °C 4 3 °C
2
Use Cooling
only indoor
unit for HR
5 2.5 °C 5 2.5 °C 5 3.5 °C
6 3 °C 6 3 °C 6 4 °C
7 3.5 °C 7 3.5 °C 7 4.5 °C
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation PAGE
(When setting SEG3)
Standard for mode
ʀ˵ɇ˝ʪAͱͱ˝
Heating
(When setting SEG3)
Time required for mode
change
Compensation option
for Long pipe or height
difference between indoor
units
MTFC (*3)
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details
1
0 1 °C 0 5min 0 Default
0 Default
11.5 °C1 7min
1
(*1) Height
difference is
more than
30m or
(*2) Distance
is longer than
110m
22 °C2 9min
3 2.5 °C 3 11min
43 °C4 13min
2
(*1) Height
difference is
15~30m or
(*2) Distance
is 50~110m
2Use
53.5 °C5 15min
64 °C620min
74.5 °C7 30min