44
K3(Number of press) KEY operation Display on segment
1 time Initialize (Reset) setting Same as initial state
K4(Number
of press)
KEY operation
Display on segment
SEG 1 SEG2, 3, 4
1 time Outdoor unit model 1
5HP (AM048*XM*) 0, 0, 5
2 times Order frequency of compressor 2
120 Hz 1,2,0
3 times High pressure 3
1.52 MPa 1, 5, 2
4 times Low pressure 4
0.43 MPa 0, 4, 3
5 times Discharge temperature of compressor 5
188.6 °F(87 °C) 0, 8, 7
6 times IPM temperature of compressor 6
188.6 °F(87 °C) 0, 8, 7
7 times CT sensor value of compressor 7
2 A 0, 2, 0
8 times Suction temperature 8
-43.6 °F(-42 °C) -, 4, 2
9 times COND OUT temperature 9
-43.6 °F(-42 °C) -, 4, 2
10 times Liquid pipe temperature A
-43.6 °F(-42 °C) -, 4, 2
11 times TOP temperature of compressor B
188.6 °F(87 °C) 0, 8, 7
12 times Outdoor temperature C
-43.6 °F(-42 °C) -, 4, 2
13 times EVI inlet temperature D
-43.6 °F(-42 °C) -, 4, 2
14 times EVI outlet temperature E
-43.6 °F(-42 °C) -, 4, 2
15 times Main EEV step F
2000 steps 2, 0, 0
16 times EVI EEV step G
300 steps 3, 0, 0
17 times Fan step H
13 steps 0, 1, 3
18 times Current frequency of compressor I
120 Hz 1,2,0
19 times
Master indoor unit address
(Master indoor unit can be selected by
wired remote-controller)
J
Master indoor unit not selected BLANK , N , D
If indoor unit No.1 is selected as the master unit 0 , 0 , 1
20 times MCU Bypass EEV Step K
300 steps 3, 0, 0
K4 (Press and hold for 2 seconds
to enter the setting) K4
press (Number of press)
Displayed content
Display on segment
Page 1 Page 2
1 time Main version MAIN Ver. (ex) 1412)
2 times Inverter version INV1 Ver. (ex) 1412)
3 times EEP version EEP Ver. (ex) 1412)
4 times
Assigned address of
the units
AUTO
SEG 1,2 SEG 3,4
Indoor unit: “A" , "0"
HR Changer/MCU Unit
: “C”, “1”
Address (ex) 07)
5 times
Manually assigned
address of the units
MANU
SEG 1,2 SEG 3,4
Indoor unit: “A" , "0" Address (ex) 15)