43
ENGLISH
Setting outdoor unit option switch and key function
After installing the product, be sure to perform leak tests on the piping connections. After pumping down
refrigerant to inspect or relocate the outdoor unit, be sure to stop the compressor and then remove the
connected pipes.
- Do not operate the compressor while a valve is open due to refrigerant leakage from a pipe or an
unconnected or incorrectly connected pipe. Failure to do so may cause air to flow into the compressor and
too a high pressure to develop inside the refrigerant circuit, leading to an explosion or product malfunction.
WARNING
Setting key operation and checking the view mode with tact switch
K1 Control KEY operation Display on segment
Press and hold 1 time Auto trial operation “K” ”K” “BLANK” “BLANK
K1(Number of press) KEY operation Display on segment
1 time Refrigerant charging in Heating mode
(Note 1)
“K” ”1” “BLANK” “BLANK”
2 times Trial operation in Heating mode
(Note 1)
“K” ”2” “BLANK” “BLANK”
3 times Pump out in Heating mode
(Note 1)
“K” ”3” “BLANK” “1”
4 times Vacuuming “K” ”4” “BLANK “1”
5 times End Key operation
K2(Number of press) KEY operation Display on segment
1 time Refrigerant charging in Cooling mode “K” ”5” “BLANK” “BLANK”
2 times Trial operation in Cooling mode “K” ”6” “BLANK “BLANK
3 times Pump down in Cooling mode “K” ”7” “BLANK “BLANK
4 times
Automatic setting of operation mode
(Cooling/Heating) for trial operation
“K” ”8” “BLANK” “BLANK”
5 times Checking the amount of refrigerant
“K” “9” “X” “X”
(Display of last two digits may differ
depending on the progress)
6 times Discharge mode of DC link voltage “K”A “BLANK” “BLANK”
7 times Forced defrost operation “K ”B” “BLANK” “BLANK”
8 times Forced oil collection “K” ”C” “BLANK” “BLANK”
9 times Inverter compressor check “K” ”D” “BLANK” “BLANK”
10 times
H/R : Auto pipe pairing
H/P : Unused
K H” “ X ” “ X
(Display of last two digits may differ
depending on the progress)
11 times End Key operation
Even when the outdoor unit power is off, it is dangerous when you come in contact with inverter PCB since it is charged
with high DC voltage.
When replacing/repairing the PCB, cut-off the power and wait until the DC voltage is discharged before replacing/
repairing them. (Wait for more than 15 minutes to allow it to discharge naturally.)
When there were error, 'Discharge mode of DC link voltage' may not have been effective. Especially if error E464 has been
occurred, power element might be damaged by fire and therefore, do not use the 'Discharge mode of DC link voltage'.
During "Discharge mode of DC link voltage", voltage of INV will be displayed.