42
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Channel
address
Main 1 3
AU
Automatic setting
(factory default)
Address for classifying the
product from upper level
controller(DMS,S-NET 3,etc.)
0 - 15
Manual setting for channel
0 – 15
Snow
accumulation
prevention
control
Main 1 4
0 0 Enabled
During snow accumulation ,
the fan may spin even when
the unit is not in operation
01
Disabled
(Factory default)
Unused
option
Main 1 5 0 0 Unused option Unused option by this model
Unused
option
Main 1 6 0 0 Unused option Unused option by this model
Unused
option
Main 1 7 0 0 Unused option Unused option by this model
Max. capacity
restriction
Main 1 8
0 0 Enabled (Factory default)
Restrict excessive capacity
increase when operating
indoor units with small
capacity
0 1 Disabled
Gas leak
pump down
Main 1 9
00
Disabled
(Factory default)
If the gas leak occurred it
should be entered in the
pump down operation.
0 1 Enabled
Unused
option
Main 2 0 0 0 Unused option Unused option by this model
Unused
option
Main 2 1 0 0 Unused option Unused option by this model
Emergency
operation for
indoor unit
communication
error
Main 2 2
0 0 Disabled (Factory default)
When set, emergency
operation is possible even
if an indoor communication
error occurs.
01
Indoor high humidity
condition
(operating for up to 12hours)
02
Indoor low humidity
condition
(operating for up to 24hours)
Base Heater Main 2 3
0 0 Disabled
0 1 Enabled
There is a risk of water leakage during emergency operation for indoor unit communication error. Please be careful when
using it.