Troubleshooting
346 Samsung Electronics
4-4-22 SPI Feedback Error
1. How to check
Is the SPI connector of an
indoor unit separated from PCB?
Connect the connector to PCB
and reoperate
Yes
No
Replace Main PCB
Can you measure 12V from
#1, #4 power with SPI connector
being connected?
Replace SPI
No
Yes
#1 #4
Outdoor unit display
Indoor unit display
(Operation)
(Timer)
×(Fan)
(Filter)
×(Defrost)
Criteria
• Check if the output of SPI Feedback is 12V
Cause of problem
• SPI defect