Product Specifications
12 Samsung Electronics
Model
AM028HNNDEH/TL AM036HNNDEH/TL AM045HNNDEH/TL
Power Supply
1,2,220-240,50 1,2,220-240,50 1,2,220-240,50
Mode*1)
HP/HR HP/HR HP/HR
Performance
Capacity
(Nominal)
Cooling*2)
kW
2.8 3.6 4.5
Btu/h
9,600 12,300 15,400
Heating*3)
kW
3.2 4 5
Btu/h
10,900 13,600 17,100
Power
Power Input
(Nominal)
Cooling*2) W
120 120 120
Heating*3)
120 120 120
Current Input
(Nominal)
Cooling*2) A
0.87 0.87 0.89
Heating*3)
0.87 0.87 0.89
Fan
Motor
Type -
Turbo Fan Turbo Fan Turbo Fan
Output W
40 x 1 40 x 1 40 x 1
Air Flow Rate H/M/L (UL) CMM
11.8/10.8/9.8 12/11/10 13/12/11
External
Pressure
Min / Std / Max
mmAq
---
Pa
---
Piping
Connections
Liquid (Flare)
ø, mm
6.35 6.35 6.35
ø, inch
1/4" 1/4" 1/4"
Gas (Flare)
ø, mm
12.70 12.70 12.70
ø, inch
1/2" 1/2" 1/2"
Drain (Quick Lock) ø, mm
VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Field
Wiring
Power Source Wire mm²
2.5 2.5 2.5
Transmission Cable mm²
VCTF 0.75 ~ 1.5 VCTF 0.75 ~ 1.5 VCTF 0.75 ~ 1.5
Refrigerant
Type -
R410A R410A R410A
Control Method -
EEV INCLUDED EEV INCLUDED EEV INCLUDED
Sound Sound Pressure H/M/L dBA
40 / 36 / 34 40 / 36 / 34 43 / 41 / 38
Dimensions
Net Weight
ΜΘ
16.0 16.0 16.0
Shipping Weight
ΜΘ
18.4 18.4 18.4
Net Dimensions (W x H x D)
ΞΞ
575 x 260 x 575 575 x 260 x 575 575 x 260 x 575
Shipping Dimensions (W x H x D)
ΞΞ
669 x 339 x 644 669 x 339 x 644 669 x 339 x 644
Panel Size
Panel model -
PC4SUSE1N PC4SUSE1N PC4SUSE1N
Panel Net Weight kg
3.0 3.0 3.0
Shipping Weight kg
5.0 5.0 5.0
Net Dimensions (W×H×D) mm
670 x 35 x 670 670 x 35 x 670 670 x 35 x 670
Shipping Dimensions (W×H×D) mm
723 x 117 x 723 723 x 117 x 723 723 x 117 x 723
Additional
Accessories"
Drain pump
Drain pump - / Model
Built-in Built-in Built-in
Max. lifting
Height /
Displacement
mm/liter/
h
750/24 750/24 750/24
Air Filter -
Pre filter Pre filter Pre filter
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.
Indoor Unit (cont.)
Ŷ 4Way Cassette(600x600)