EasyManua.ls Logo

Samsung AM028JNVDKH/EU - Liquid Compression Prevention Control

Samsung AM028JNVDKH/EU
552 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Samsung Electronics 403
1. Inspection Method
4-4-80 Liquid Compression Prevention Control
Are the SUMP sensor
and the discharge sensor are properly
connected/attached?
Check the failure in
liquid bypass valve and
4way valve.
Check the normal EEV operation
of the main EEV EVI.
Check and change the discharge valve leakage.
Re-check the sensor connection/attachment.
No
Normal
Normals
Yes
Breakdown
Breakdown
Resolve the relevant EEV problem.
Resolve the relevant valve problem.
Outdoor Unit Display
Indoor Unit Display
-
Judgment Method • SUMP temperature decrease & DSH < 5°C 25 min.
Special Cause
EVI EEV and super cooler, liquid bypass valve leakage, refrigerant overcharge, indoor unit EEV leakage,
direct connection between indoor liquid pipe-gas pipe, faulty main EEV, and failure to operate compressor

Table of Contents

Related product manuals