EasyManua.ls Logo

Samsung AM036FNMDCH/AA - Inverter Overcurrent Error

Samsung AM036FNMDCH/AA
370 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Samsung Electronics 4-109
4-4-75 Inverter Overcurrent error
Outdoor unit display
(INVERTER1 PCB)
(INVERTER2 PCB)
Judgment Method
Will occur if the overcurrent flowing in the IPM.
 Detected by H/W or S/W
Cause of problem
 Installation defective
 Comp. defective
 PCB defective
 Connection wire error
 Motor defective
Power Off
Continue
Ye s
Is the outdoor unit installed properly?
Remove the obstacles and check
the status of the installation.
No
Ye s
Is temperature
sensor location and the measurement
value normally?
Power Off, and then replacement
or correction of the sensor location
No
Ye s
Is the resistance value
between phase of Compressor wire
(U-V, V-W, W-U) less than 2?
Replace Compressor
No
Ye s
Is the resistance between
the body of Compressor and
chassis M?
Replace Compressor
No
Ye s
Does the Compressor
connection wire properly connect
to the compressor?
Check the connection wire
(Check the status of the connection UVW)
No
1.
Cause of problem

Table of Contents

Related product manuals