EasyManua.ls Logo

Samsung AM036FNMDCH/AA - Page 49

Samsung AM036FNMDCH/AA
370 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product Specifications
Samsung Electronics 2-45
Model
OAP Duct
AM072JNESCH/AA AM096JNESCH/AA
Power Supply φ,V,Hz 1,208~230,60 1,208~230,60
Mode
1)
-HP HP
Performance Capacity
Cooling
2)
Btu/hr 92%װ 72,000 96,000
Heating
3)
Btu/hr 92%װ 47,000 59,000
Power
Input Consumption (Cooling/Heating) W 105%ײ 360/360 450/450
Running Current (Cooling/Heating) A 105%ײ 2.60/2.60 3.10/3.10
Indoorunit refrigerant adding amount Kg/EA 1.18 1.18
Noise Level Actual Noise Pressure (High) dB(A)ײ 47 47
Fan
Type - Sirocco, Φ270*2EA Sirocco, Φ270*2EA
Motor
Model - DL-17860SSBA (DB31-00659A) DL-17860SSBA (DB31-00659A)
Type - BLDC Feedback BLDC Feedback
Output W - -
Fan Speed
Fan(H/M/L) 0 mmAq
rpm±20
875/-/- 890/-/-
Fan(H/M/L) Standard 1050/-/- 1080/-/-
Cooling (H/M/L) Standard - -
Heating (H/M/L) Standard - -
Airflow Rate
Fan(H/M/L)
/min
28.00/-/- 35.00/-/-
Cooling (High) - -
Heating (High) - -
Refrigerant
Type - R410a R410a
Control Method - EDM EEV 6.4C EDM EEV 6.4C
Temperature Control - Micom&Thermistors Micom&Thermistors
Safety Devices - Fuse Fuse
External Static Pressure Standard (Min.~Max) mmH2O 25(5~30) 25(5~30)
Piping
Connections
Liquid (F
lare)
Φ,mm 9.52 9.52
Φinch 3/8 3/8
Gas (Flare)
Φ,mm 19.05 22.23
Φinch 3/4" 7/8"
Drain
Φ,mm VP25 (OD 32,ID 25) mm VP25 (OD 32,ID 25) mm
Φinch - -
Weight
Net Weight kg 90 90
Shipping Weight kg 100 100
Dimensions
Net Dimensions (W×H×D)
mm 1465x460x910 1465x460x910
inch - -
Shipping Dimensions (W×H×D)
mm 1612 x 519 x 984 1612 x 519 x 984
inch - -
Bypass Tube
SOLENOID VALVE - Assy,FDF6A48 Assy,FDF6A48
Check VALVE - ID9.6-ID12.9 ID9.6-ID12.9
Panel Size
Model - - -
Net Weight kg - -
Shipping Weight kg - -
Net Dimensions (W×H×D) mm - -
Shipping Dimensions (W×H×D) mm - -
Functions
Auto restart - O O
Auto swing - X X
Group/Individual control - O(OAP group only) O(OAP group only)
External contact control - O O
Trouble shooting by LED - X X
Standard
accessories
Installation manual - O O
Operation manual - O O
Pattern sheet for installation - O O
Flexible drain hose - O O
Filter/Safety grille - X X
Drain pump
Drain pump - / Model Name Optional / MDP-G075SQ Optional / MDP-G075SQ
Max. lifting Height / Displacement mm / liter/h 750 / 24 750 / 24
Optional
Accessories
Wireless remote controller - MR-EH00U MR-EH00U
Wired remote controller - MWR-WE10N MWR-WE10N
External contact interface module - MIM-B14 MIM-B14
Duct Receiver kits - MRK-A10N MRK-A10N
EEV kits - - -
Indoor Unit(cont.)
QOAP Duct
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Norminal cooling capacities are based on;
- Indoor temperature : 35ఁDB, 28ఁWB - Outdoor temperature : 35ఁDB, 28ఁWB
*3) Norminal heating capacities are based on;
- Indoor temperature : 0ఁ DB, -3ఁWB - Outdoor temperature : 0ఁDB, -3ఁWB
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.