EasyManua.ls Logo

Samsung AM036FNMDCH/AA - Page 51

Samsung AM036FNMDCH/AA
370 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product Specifications
Samsung Electronics 2-47
Model
Global Duct 1
AM012MNMDCH/AA AM015MNMDCH/AA AM018MNMDCH/AA
Power Supply Φ, #, V, Hz 1,2,208-230,60 1,2,208-230,60 1,2,208-230,60
Mode - HP/HR HP/HR HP/HR
Performance
Capacity
(Nominal)
C
ooling 2)
kW - - -
Btu/h 12,000 15,000 18,000
Heating 2)
kW - - -
Btu/h 13,500 17,000 20,000
Condensate
(with high fan speed)
Lit
er/h - - -
Power
Power Input
(Nominal)
C
ooling 1) W 31 38 80
Heating 2) W 31 38 80
Current Input
(Nominal)
C
ooling 1) A 0.26 0.30 0.65
Heating 2) A 0.26 0.30 0.65
Fan
Type - Sirocco Fan Sirocco Fan Sirocco Fan
Motor
Model -
Type - BLDC BLDC BLDC
Output x n W 153 x 1 153 x 1 153 x 1
Air Flow Rate H/M/L CMM 10 11 17
External
Pressure
M
in / Std / Max
mmAq 0.0 / 1.0 / 15.0 0.0 / 1.0 / 15.0 0.0 / 1.0 / 15.0
Pa 0.0 / 9.8 / 147.1 0.0 / 9.8 / 147.1 0.0 / 9.8 / 147.1
Sound
Sound Pressure High / Mid / Low dB(A) 27 / 25 / 23 28 / 26 / 24 29 / 27 / 25
Sound Power Cooling dB(A) - - -
Refrigerant
Type - R410A R410A R410A
Control Method - EEV INCLUDED EEV INCLUDED EEV INCLUDED
Temperature Control - Micom&Thermistors Micom&Thermistors Micom&Thermistors
Safety Devices - Fuse Fuse Fuse
Piping
Connections
Liquid Pipe (Flare)
Φ,mm 6.35 6.35 6.35
Φ, inch 1/4" 1/4" 1/4"
Gas Pipe (Flare)
Φ,mm 12.7 12.7 12.7
Φ, inch 1/2" 1/2" 1/2"
Drain Pipe (Quick lock) Φ,mm VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Dimensions
Net Weight kg 3.15 3.15 3.15
Shipping Weight kg 35.5 35.5 35.5
Net Dimensions (W×H×D) mm 850 x 250 x 700 850 x 250 x 700 850 x 250 x 700
Shipping Dimensions (W×H×D) mm 1,064 x 320 x 784 1,064 x 320 x 784 1,064 x 320 x 784
Funtion
Auto restart - o o o
Auto swing - x x x
Group/Individual control - o o o
Exteral contact control - o o o
Trouble shooting by LED - x x x
Standard
accessories
I
nstallation manual - o o o
Operation manual - o o o
Pattern sheet for installation - x x x
Flexible drain hose - o o o
Flilter/Safety grille - Long life filter Long life filter Long life filter
Drain pump
Drain pump - Built-In Built-In Built-In
Max. lifting Height
/ Displacement
mm / liter/ h
750 / 24 750 / 24 750 / 24
Optional
accessories
W
ireless remote controller - MR-DH00U MR-DH00U MR-DH00U
wired remote controller - MWR-WE10N MWR-WE10N MWR-WE10N
External contact interface module - MIM-B14 MIM-B14 MIM-B14
Duct Receiver kits - MRK-A10N MRK-A10N MRK-A10N
EEV kits - - - -
Indoor Unit(cont.)
QGlobal Duct 1
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.