72 Samsung Electronics
Check Operation & Amount of Refriherant Automatically Checking
3) Pressure sensor
Ŷ Inspection item : High/Low Pressure sensor of the independent installed Outdoor Unit.
ŶError code: None (The resulting report "Undetermined")
Ŷ Determine the status of the Pressure sensor of the independent installed Outdoor Unit before the compressor start.
Ŷ If the judgment of Outdoor Unit Pressure sensor is "Undetermined" : Checking in accordance with the following order.
Yes
No
Yes
No
Yes
No
[Caution]
- If the Outdoor Unit with a history of operation (Automatic commissioning inclusion) : Maintain the vacuum mode for more than 5 minutes.
Vacuum mode of Outdoor Unt
Check the pressure sensor breakdown
Is Pressure
sensor connector properly connect
Is voltage 5V between
3, 4 pin of PCB Pressure sensor
terminal?
Is deviation
of outdoor unit as following?
High pressure Max/Min deviation :
less than 2
Off the vauum mode Outdoor Unit
Complete
Confirmation and Measures
Replace Hub PCB
Replace PCB
Check the Pressure sensor breakdown after the saturation pressure of the
outdoor temperature or connect the manifold gauge to check the pressure