54
Setting an indoor unit address and installation option
Setting an indoor unit installation option (suitable for the condition of each installation location)
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2. The panel(display) should be connected to an indoor unit to receive option.
3. Set the installation option according to the installation condition of an air conditioner.
- The default setting of an indoor unit installation option is “020000-100000-200010-300000
- Individual control of a remote controller(SEG20) is the function that controls an indoor unit individually when there is
more than one indoor unit.
4. Set the indoor unit option by wireless remote controller.
■ 02 series installation option
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
0 2 - - Central control -
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1---
Opening the
electronic
expansion valve
-
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2 External control
External control
output
---
SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
3-
Heating setting
compensation
EEV opening of
an indoor unit
stopped during oil
return or Defrost
operation.
--
f If you input a number other than 0~4 of the individual control of the indoor unit(SEG20), the indoor is set as “indoor 1”.
f SEG5 option for centralized control usage is set to 0(disuse) as a default setting. You must adjust the setting for this option
separately when centralized control needs to be used.
■ 02 series installation option(Detailed)
Option No. : 0AXXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation
PAGE MODE Use of robot cleaning
Use of external
temperature sensor
Use of central
control
FAN RPM
compensation
Remote
Controller
Display
Indication
and Details
Indication Details Indication
Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
02
0 Disuse 0 Disuse 0 Disuse 0 Disuse
1Use