KEY OPTION
Tact S/W # of Times Item SEG1 SEG2 SEG3 SEG4 Note
K1 Auto Commissioning & Management System
One time of
long press
K1
1time Charge heating refrigerant
2times Test heating operation
3times Heating pump out
4times Vacuum
5times Finish
K2
1time Charge cooling refrigerant
2times Test cooling operation
3times Cooling pump down
4times Test operation for checking refrigerant level
5times Finish
K3 Reset
Tact S/W # of Times Item SEG1 SEG2 SEG3 SEG4 Note
K1
1time Charge heating refrigerant
2times Test operation of heating
3times Heating pump out
4times Vacuum
5times Finish
K2
1time Charge cooling refrigerant
2times Test operation of cooling
3times
Cooling pump down
4times Finish
K3 Reset
Ŷ AM66666M666 series
Ŷ RD666M6666 series
Ŷ K4 Display Order
K4 Di splay Detai ls
Display Value (Ex.) Meaning
SEG1 SEG 2,3,4
1time Operating fr equency of curr ent compressor 1 0,4,2 42Hz
2times
Low pressure value (AM66666M666 series ) 2 1,7,5 1.75Mpa
Target fr eq uency (RD666M6666 series ) 0,6,4 64Hz
3times Outdoor temperature 3 1,5,8 15.8ఁ
4times Discharge temperature of compressor 4 7,7,277.2ఁ
5times OLP temperature 5 5 ,5,855.8ఁ
6times C OND temperature 6 3,1,731.7 ఁ
7times Double-pipe heat exchanger temperature 7 1,8,9 18.9ఁ
8times High pres sure value82,1,02.10MPa
9times Outdoor fan RPM 9 6,0,0 600 RPM
10times ESC (EVI) EEV Operating ValueA0,8,080 STEP
11times MAIN EEV Operating Value B1,0,0 1000 STEP
12times Current ValueC1,0,0 10A
13times Number of Indoor Unit Connections D 0,0,77ఁ
14times Number of Indoor Units Operating E 0,0,4 4ఁ
15times Total Capacity of Connected Indoor Units F1,4,5 14.5kcal/hr