21
ENGLISH
❋ When the equivalent length between an outdoor unit and the farthest indoor unit exceeds 90m (295’), upgrade the low
pressure pipe of the main pipe one step.
❋ Note 1) When indoor unit is located at higher level than outdoor unit, allowable height dierence is 40m(131ft), but
when the indoor unit is located at lower level than outdoor unit, allowable height dierence is 50m(164ft).
Refrigerant pipe work
Refrigerant Y-joint installation
Install the Y-joint ‘horizontally’ or ‘vertically’.
X Install horizontally
X Install vertically
t When using A~J type of Y-joint, connect the Y-joint to the pipe with the provided reducer.
t When using K~Z type of Y-joint, connect the Y-joint to the pipe by cutting the inlet of the Y-joint or provided
reducer properly.
10~15mm (0.39~0.59inch)
or more
NOTE
t Install the Y-joint within ±15° on the horizontal or on the vertical.
t Make sure that the pipe does not break at Y-joint and pipe connection.
t Keep a minimum straight line distance of 500mm (20inch) or more before connecting Y- joint.
±15°
❋ Install the Y-joint within ±15° on the
horizontal or on the vertical.
Minimum straight line distance
[500mm (20inch) or more]
Main pipe
Connect to
outdoor unit
Pipe
Front
Gas/liquid side Y-joint
Rear
Rear
Pipe connection
Reducer
Reducer
Connect to other branch
joint or indoor unit
CAUTION