26
Refrigerant pipe installation
Selecting additional refrigerant charging
X Basic refrigerant
The basic amount of additional refrigerant charged at a factory
Model Refrigerant
Factory charge
kg lbs
AM060MXMDCH✴ R410A 3.7 8.2
X Charging additional refrigerant
The amount of additional refrigerant charging =
The amount of refrigerant charging for pipe +
the amount of refrigerant correction charging for an indoor unit.
1) The amount of additional refrigerant depending on the pipe size.
- Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Size of liquid pipe [mm(inch)] 6.35 (1/4) 9.52 (3/8) 12.7 (1/2) 15.88 (5/8)
Additional amount [kg/m (lb/ft)] 0.02 (0.013) 0.06 (0.040) 0.125 (0.084) 0.18 (0.121)
Additional refrigerant charging calculation = The sum of total length of Ø 9.52 liquid pipe(m) x 60g + the sum of
total length of Ø 6.35 liquid pipe(m) x 20g
Ex) a(Ø 9.52)=40m(131.23’), b+c+d(Ø 9.52)=15m(49.21’), e+f+g(Ø 6.35)=15m(49.21’)
The amount of additional refrigerant = 55m(180.45’) x 60g + 15m(49.21’) x 20g = 3600g
2) The amount of additional refrigerant for each indoor unit
[Unit: kg(lb)]
Capacity(kBtu)
Model
6 7.5 9 9.5 12 15 18 20 24 27 30 36 48 54
1way cassette
(AM✴✴✴FN1DC✴/AA)
0.25
(0.55)
0.25
(0.55)
0.25
(0.55)
Mini 4way cassette S (600x600)
(AM✴✴✴FNNDC✴/AA)
0.37
(0.82)
0.37
(0.82)
0.37
(0.82)
0.37
(0.82)
4way cassette
(AM✴✴✴FN4DC✴/AA)
0.45
(0.99)
0.45
(0.99)
0.45
(0.99)
0.69
(1.52)
0.69
(1.52)
0.69
(1.52)
360 cassette
(AM✴✴✴KN4DC✴/AA)
0.45
(0.99)
0.45
(0.99)
0.45
(0.99)
0.45
(0.99)
0.69
(1.52)
0.69
(1.52)
0.69
(1.52)
Floor Standing Unit
(AM✴✴✴JNFDC✴/AA,
AM✴✴✴JNGDC✴/AA)
0.12
(0.26)
0.22
(0.49)
0.22
(0.49)
0.32
(0.72)
0.32
(0.72)
Slim duct
(AM✴✴✴FNLDC✴/AA)
0.24
(0.53)
0.24
(0.53)
0.24
(0.53)
0.45
(0.99)
0.45
(0.99)
0.45
(0.99)
0.45
(0.99)
0.62
(1.37)
MA duct
(AM✴✴✴JNMDC✴/AA)
0.37
(0.81)
0.37
(0.81)
0.37
(0.81)
0.54
(1.19)
0.54
(1.19)
0.47
(1.04)
0.47
(1.04)
0.47
(1.04)
0.68
(1.50)
0.68
(1.50)
MSP duct
(AM✴✴✴FNMDC✴/AA)
0.28
(0.62)
0.28
(0.62)
0.54
(1.19)
0.54
(1.19)
0.68
(1.50)
HSP duct
(AM✴✴✴FNHDC✴/AA)
0.68
(1.50)
0.68
(1.50)
Wall mounted
(AM✴✴✴FNTDC✴/AA)
0.24
(0.53)
0.24
(0.53)
0.24
(0.53)
0.36
(0.79)
0.36
(0.79)
0.36
(0.79)
Ceiling
(AM✴✴✴FNCDC✴/AA,
AM✴✴✴JNCDC✴/AA)
0.39
(0.86)
0.39
(0.86)
0.56
(1.23)
0.95
(2.09)