Even when the outdoor unit power is off, it is dangerous when you come in contact with inverter PCB since it is
charged with high DC voltage.
When replacing/repairing the PCB, cut-o the power and wait until the DC voltage is discharged before replacing/
repairing them. (Wait for more than 15 minutes to allow it to discharge naturally.)
When there were error, 'Discharge mode of DC link voltage' may not have been eective. Especially if error E464 has
been occurred, power element might be damaged by re and therefore, do not use the 'Discharge mode of DC link
voltage'.
During "Discharge mode of DC link voltage", voltage of INV will be displayed.
K3(Number of press) KEY operation Display on segment
1 time Initialize (Reset) setting Same as initial state
K4(Number
of press)
KEY operation
Display on segment
SEG 1 SEG2, 3, 4
1 time Outdoor unit model 1
7HP(AM060
7XM7) 0, 0, 7
2 times Order frequency of compressor 2
120 Hz
1,2,0
3 times High pressure 3
1.52 MPa
1, 5, 2
4 times Low pressure 4
0.43 MPa
0, 4, 3
5 times
Discharge temperature of compres-
sor
5
188.6
°F(87
°C)
0, 8, 7
6 times IPM temperature of compressor 6
188.6
°F(87
°C)
0, 8, 7
7 times CT sensor value of compressor 7
2 A
0, 2, 0
8 times Suction temperature 8
-43.6
°F(-42
°C)
-, 4, 2
9 times COND OUT temperature 9
-43.6
°F(-42
°C)
-, 4, 2
10 times Liquid pipe temperature A
-43.6
°F(-42
°C)
-, 4, 2
11 times TOP temperature of compressor B
188.6
°F(87
°C)
0, 8, 7
12 times Outdoor temperature C
-43.6
°F(-42
°C)
-, 4, 2
13 times
EVI inlet temperature
D
-43.6
°F(-42
°C)
-, 4, 2
14 times
EVI outlet temperature
E
-43.6
°F(-42
°C)
-, 4, 2
15 times
Main EEV step
F
2000
steps
2, 0, 0
16 times EVI EEV step G
300 steps
3, 0, 0
17 times
Fan step
H
13 steps
0, 1, 3
18 times
Current frequency of compressor
I
120 Hz
1,2,0
19 times
Master indoor unit address
(Master indoor unit can be selected
by wired remote-controller)
J
Master indoor unit not selected
BLANK , N , D
If indoor unit No.1 is selected as the master unit
0 , 0 , 1