Product Specications
Samsung Electronics 2-7
2-2 Product Specifications
2-2-1 Outdoor Unit
TYPE DVM S HP - 208-230V
Model AM072FXVAFH/AA AM096FXVAFH/AA AM120FXVAFH/AA AM144FXVAFH/AA
Mode HP HP HP HP
Power Ø,V,Hz 3/208-230/60 3/208-230/60 3/208-230/60 3/208-230/60
Capacity
Cooling (Nominal) Btu/h 72,000 96,000 120,000 144,000
Cooling (Rated) Btu/h 69,000 92,000 114,000 138,000
Heating (Nominal) Btu/h 81,000 108,000 135,000 162,000
Heating (Rated) Btu/h 77,000 103,000 129,000 154,000
Power Consumption
(Nonducted, AHRI)
Cooling W 5,350 6,680 9,140 12,340
Heating W 5,430 7,130 9,520 12,400
current consumption
(Nonducted, AHRI)
Cooling A 14.6 18.2 24.9 33.7
Heating A 14.8 19.5 26.0 33.8
EER
(Nonducted, AHRI)
Cooling Btu/Wh 12.9 13.8 12.5 11.2
Heating W/W 4.15 4.23 3.97 3.64
IEER(AHRI) Cooling W/W 23.0 26.0 24.2 22.7
Compressor
Model - DS-GB052FBVASG DS-GB052FBVASG DS-GB052FBVASG DS-GB052FBVASG
Output kW 33.1 33.1 33.1 33.1
Excluded Volume cc/rev 52.0 52.0 52.0 52.0
Capacity Btu/h 58,000 58,000 58,000 58,000
Quantity EA 1 2 2 2
Lubricant oil
Type Liter FV68D(PVE) FV68D(PVE) FV68D(PVE) FV68D(PVE)
Factory Charging Liter 3.9 6.2 6.2 6.2
Refrigerant
Type - R410A R410A R410A R410A
Factory Charging lb 12.13 16.31 16.31 19.18
FA N
Ø mm 700 575 575 575
MAX STEP - 19 29 29 31
CODE - DB31-00298A DB94-03285C DB94-03285C DB94-03285C
MAX RPM STEP(RPM) 800 1050 1050 1100
Quantity EA 1 2 2 2
CMM 205 260 260 270
Piping
Connections
Gas Inch 3/4"(19.05) 7/8"(22.22) 1+1/8"(28.58) 1+1/8"(28.58)
Dis. Gas Inch - - - -
Liquid Inch 3/8"(9.52) 3/8"(9.52) 1/2"(12.7) 1/2"(12.7)
DIMENSION
NET mm 880x1695x765 1295x1695x765 1295x1695x765 1295x1695x765
GROSS mm 948x1912x832 1363x1912x832 1363x1912x832 1363x1912x832
NET kg 190 278 278 293
GROSS kg 206 300 300 312
Operating Temp.
Range
Cooling
ሥ
23~118 23~118 23~118 23~118
Heating
ሥ
-4~75 -4~75 -4~75 -4~75
1. Proper form capacity standard of air conditioning
- Cooling capacity : It is figures that appear in indoor 80.6 ሥ DB/66.2 ሥ WB, outdoor 95 ሥ DB, length 50m of piping, fall 0m standard.
- Heating capacity : It is figures that appear in indoor 68 ሥ DB, outdoor 44.6 ሥ DB, length 50m of piping, fall 0ft standard.
2. If proper form heating capacity is outdoor temperature 44.6 ሥ standard and outdoor temperature goes down by below zero,
heating capacity can drop according to temperature condition.
3. Need special load calculation in case of use by main heating in the winter, and please buy product for low temperature that heating effect excels at low temperature.
4. Maximum length between outdoor and indoor units allows up to 656ft (Equivalent length 722ft).
5. If the indoor unit is below, height length allows up to 361ft (If over 164ft, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 131ft.