26
Wiring Work
5. Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation
tape.
A total of three or more layers of insulation is required.
X Method 1
40 mm
Insulation tape
X Method 2
Insulation tape
35 mm
6. Apply heat to the contraction tube to contract it.
Contraction tube
7. After tube contraction work is completed, wrap it with the insulation tape to nish.
Make sure that the connection parts are not exposed to outside.
Be sure to use insulation tape and a contraction tube made of approved reinforced insulating materials
that have the same level of withstand voltage with the power cable. (Comply with the local regulations
on extensions.)
CAUTION
Insulation tape
In case of extending the electric wire, please DO NOT use a round-shaped Pressing socket.
- Incomplete wire connections can cause electric shock or a re.
WARNING
NASA_Big Duct_AM@@@FNHDEH@_IM_03864A-05_EN.indd 26 2016-04-01 오후 5:29:45