34
Setting an indoor unit address and installation option
05 series installation option
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
0 5
Use of Auto Change Over
for HR only in Auto mode
(When setting SEG3)
Standard heating temp.
Oset
(When setting SEG3)
Standard cooling temp.
Oset
(When setting SEG3)
Standard for mode change
Heating Cooling
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1
(When setting SEG3)
Standard for mode
change
Cooling Heating
(When setting SEG3)
Time required for mode
change
Compensation option
for Long pipe or height
dierence between
indoor units
- -
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2 - - - -
Control variables when
using hot water / external
heater
SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
3 - - - - -
05 series installation option(Detailed)
Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation PAGE MODE
Use of Auto Change
Over for HR only in
Auto mode
(When setting SEG3)
Standard heating temp. Oset
(When setting SEG3)
Standard cooling temp.
Oset
(When setting SEG3)
Standard for mode
change
Heating Cooling
Remote Controller
Display
Indication and
Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
0 5
0
Follow
product
option
0 0 0 0 0 1
1
Use Auto
Change
Over for HR
only
1 0.5 1 0.5 1 1.5
2 1 2 1 2 2
3 1.5 3 1.5 3 2.5
4 2 4 2 4 3
5 2.5 5 2.5 5 3.5
6 3 6 3 6 4
7 3.5 7 3.5 7 4.5
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation PAGE
(When setting SEG3)
Standard for mode
change
Cooling Heating
(When setting SEG3)
Time required for mode
change
Compensation option for Long
pipe or height diference
between indoor units
Remote Controller
Display
Indication and
Details
Indication Details Indication Details Indication Details Indication Details
1
0 1 0 5 min. 0 Use default value
1 1.5 1 7 min.
1
1) Height dierence
(*1)
is more than 30m
or
2) Distance
(*2)
is longer
than 110m
2 2 2 9 min.
3 2.5 3 11 min.
4 3 4 13 min.
2
1) Height
dierence
(*1)
is
15~30m
or
2) Distance
(*2)
is
50~110m
5 3.5 5 15 min.
6 4 6 20 min.
7 4.5 7 30 min.