EasyManua.ls Logo

Samsung AM280KXVAGH/EU - E269: Suction Temperature Sensor Breakway Error

Samsung AM280KXVAGH/EU
277 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
4-40 Samsung Electronics
4-3-22 : Suction Temperature sensor breakaway error
1.
Cause of problem
Replace the PCB
Is Suction sensor
and sensor Holder accurately
attached?
Is Suction sensor
resistance value reasonable?
(Refer to theNote 1” )
Defective Sensor : Replace Sensor
No
Re-insert the sensor.
Re-attach the sensor holder.
No
Yes
Yes
NOTE1
TemperatureC)Resistance(K)
70
60
50
40
30
20
10
0
-10
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Outdoor unit
display
Indoorunit
display
Duct, Cassette (1/2 Way),Console, Celing Cassette (4/Mini4 Way) Wall-mount ed (NeoForte)
Operation Defr ost Timer Fan Filter/MPI Operation Defrost Timer F ilter Operation Timer Turbo
×× ×
◑◑
: ON : Flash ×: OFF
Judgment
Method
 Judgment Method : Difference of suction temperature of compressor starting verge and suction temperature that is
on present operation : If less than 2 for 30 minutes to keep.(Judgment at heating operation only)
Cause of
problem
Suction temperature sensor breakaway/defective.

Table of Contents