Troubleshooting
4-68 Samsung Electronics
4-3-46 Compressor starting error
Outdoor unit display
(INVERTER1 PCB)
(INVERTER2 PCB)
Judgment Method
Startup, and then if the speed increase is not normally.
Detected by H/W or S/W.
Cause of problem
Compressor connection error
Defective Compressor
1.
Cause of problem
Hub Replace PCB.
No
Replace Hot Gas Bypass Valve 1.
No
Yes
Yes
Is Hot Gas Bypass Valve 1
startup the initial power is applied?
*Hot Gas Bypass Valve1 is Open when
compressor starts to reduce
the Load .
Hot Gas Bypass
Valve initial startup does it work?
*(Check the temp. between Hot Gas Bypass
Valve 1 and Suction Pipe.
If Temp. is similar with Discharge pipe
Temp. . It works.)
Power Off and then Restart
Replace Compressor.
No
Yes
Is the resistance
value between different phases of
compressor (U ׳ V,V ׳ W,W ׳ U)
less than 2?
Replace Compressor.
No
Yes
Is the resistance
between the body of Compressor and
chassis Open?
No
Yes
Does the Compressor
connection wire properly connect to
the Inverter PBA?
Repair / Replace the wire.
Continue.