(Unit ; kg/cm²g)
AQV09EW* AQV12EW*
DB21/WB15DB27/WB19 DB32/WB23DB21/WB15DB27/WB19 DB32/WB23
10°C7.97 8.499.4010°C7.13 7.62 8.33
21°C 8.74 9.75 10.78 21°C 7.68 8.56 9.33
35°C 9.4910.6912.00 35°C 8.44 9.5110.56
43°C 9.8010.88 12.31 43°C 8.629.6210.74
9-3 Distribution chart of the Pressure
Note :
1.Please measure the refrigerant pressure after the air conditioner operates on the testing mode during more than
10 minutes.
2. There may be a much torelanc at the range not presented in this graph.
8
9
10
11
12
10 15 20 25 30 35 40
Outdoor tempe r ature [
ć
]
Ps [kg/cm
2
g]
27ć
21ć
24ć
29ć
Indoor Tem perature 32ć
7
8
9
10
11
10 20 30 40
Outdoor temperature [
ć
]
Ps [kg/cm
2
g]
27ć
21ć
24ć
29ć
Indoor Tem perature 32ć
9-3
AQV09EW*
AQV12EW*