E-16
comPleting the installation
Purging the Connected Pipes(Continued)
Refrigerant type GWP value
R410A 1975
GWP=Global Warming Potential
Indoor unit
Outdoor unit
= ( ) kg
= ( ) kg
+
= ( ) kg
Contains fluorinated greenhouse gases
covered by the Kyoto Protocol.
a
b c
d
Important information regulation regarding the
refrigerant used
This product contains fluorinated greenhouse gases covered by the Kyoto
Protocol. Do not vent gases into the atmosphere.
Please fill in with indelible ink,
-
the factory refrigerant charge of the product,
-
the additional refrigerant amount charged in the field and
-
+
the total refrigerant charge.
on the refrigerant charge label supplied with the product.
The filled-out label must be adhered in the proximity of the product
charging port (e.g. onto the inside of the stop valve cover).
Note
a. Factory refrigerant charge of the product: see unit name plate
b. Additional refrigerant amount charged in the field
( Refer to the above information for the quantity of refrigerant
replenishment.)
c. Total refrigerant charge
d. Refrigerant cylinder and manifold for charging
Charging the refrigerant under conditions of liquid by
using a liquid pipe
R410A is a mixed type of refrigerant. It is necessary for recharging under
conditions of liquid. When recharging refrigerant from the refrigerant cylinder
to the equipment, follow the instructions below.
Before recharging, check whether the cylinder has a siphon or not.
There are two ways to recharge the refrigerant.
Cylinder with siphon Cylinder without siphon
Charge the refrigerant standing
Charge the refrigerant turning the
the cylinder upright. cylinder upside down.
Note
◆ If R410A refrigerant is charged with gas, the composition of the
charged refrigerant changes and the characteristics of the
equipment vary.
◆ During the measuring operation of refrigerant quantity added use
an electronic balance. If cylinder doesn’t have syphon, upset it.
siphon