Samsung Electronics 9-3
9-3 Distribution chart of the Pressure
Note :
1. Please measure the refrigerant pressure after the air conditioner operates on the testing mode during more than
10 minutes.
2. There may be a much torelanc at the range not presented in this graph.
(Unit;kg/༆g)
DB21/WB15 DB27/WB19 DB32/WB23 DB21/WB15 DB27/WB19 DB32/WB23
10 8.2 8.8 9. 2 10 7. 12 7. 9 8. 43
21 8.6 9.4 10. 0 21 7.41 8.43 9.4
35 9.2 10.2 11.4 35 8.16 9.4 10. 9
43 9.6 10.7 12.0 43 8.6 9. 9
AQV09UG* AQV12UG*
7
8
9
10
11
12
10 20 30 40
Outdoor Temperature []
Ps [kg/cm
2
g]
In d o o r Temperature 3 2
29