EasyManua.ls Logo

Samsung AR 24 RXFPEWQX - Compressor Wire Missing Error;Rotation Error

Samsung AR 24 RXFPEWQX
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
89
10-2-11 Compressor wire missing error/rotation error
Indoor display
3-LED DISPLAY
7-SEG DISPLAY DESCRIPTION
LED1 LED2 LED3
E467 Compressor wire missing errorr/rotation error
Outdoor display
Compressor wire missing error/rotation error
LED ON
LED BLINKING
LED OFF
1. Checklist :
1) Is the connection of cable for the compressor?
2) Is the compressor wire is connected clockwise? U(RED)-V(BLU)-W(YEL)
3) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
NO
NO
NO
NO
YES
YES
YES
YES
Restart after power off.
Is the restart error occurred again?
Is the connection of
compressor wire is normal?
(PBA and Compressor)
Is the restart error occurred again?
Is the compressor body and
interphase resistance insulated?
Exchange the compressor
Exchange the Outdoor PBA
Terminate the service
Connect the comp wire normally
Terminate the service

Table of Contents