22
English
Installation
• the additional refrigerant amount charged
in the field and
• + the total refrigerant charge. on the
refrigerant charge label supplied with the
product.
Refrigerant type GWP value
R-32 675
•GWP:GlobalWarmingPotential
•CalculatingtCO
2
e: kg x GWP/1000
Unit Kg tCO
2
e
①, a
②, b
①+②, c
NOTE
a Factory refrigerant charge of the product: see
unit name plate
b Additional refrigerant amount charged in the
field (Refer to the above information for the
quantity of refrigerant replenishment.)
C Total refrigerant charge
d Refrigerant cylinder and manifold for charging
CAUTION
• The filled-out label must be adhered in the
proximity of the product charging port (e.g. onto
the inside of the stop valve cover).
• Make sure that the total refrigerant charge does
not exceed (A), the maximum refrigerant charge,
which is calculated in the following formula:
Maximum refrigerant charge (A)= factory
refrigerant charge (B) + maximum additional
refrigerant charge due to piping extension (C)
• Here below, the summary table with refrigerant
charge limits for each products.
(Unit:g)
Model A B C
**09*******
**12*******
850 700 150
**18*******
**24*******
1525 1150 375