21
English
Installation Procedure
2 Select the insulation of the refrigerant pipe.
Insulate the gas side and liquid side pipe referring
to the thickness according to the pipe size.
Less than Indoor temperature of 86℉(30℃) and
humidity of 85% is the standard condition. If
installing in a high humidity condition, use one
grade thicker insulator by referring to the table
below. If installing in an unfavourable conditions,
use thicker one.
Insulator’s heat-resistance temperature should be
more than 248℉(120℃).
Pipe
Outer diameter
Insulation Type
(Cooling, Heating)
Remarks
General
[86°F(30°C),
85%]
High humidity
[86°F(30°C),
over 85%]
EPDM,NBR
mm inch mm inch mm inch
Liquid
pipe
6.35~9.52 1/4~3/8 9 3/8 9 3/8
Heating
resisting
temperature
over
248°F(120°C)
12.7~50.80 1/2~2 13 1/2 13 1/2
Gas
pipe
6.35 1/4 13 1/2 19 3/4
9.52~25.4 3/8~1 19 3/4 25 1
28.58~44.45
1 1/8~1
3/4
19 3/4 32 1 1/4
50.8 2 25 1 38 1 1/2
When installing insulation in places and
conditions below, use the same insulation that is
used for high humidity conditions.
<Geological condition>
High humidity places such as shoreline, hot spring,
near lake or river, and ridge (when the part of the
building is covered by earth and sand.)
<Geological condition>
Restaurant ceiling, sauna, swimming pool etc.
<Building construction condition>
The ceiling frequently exposed to moisture and
cooling is not covered.
e.g. The pipe installed at a corridor of a dormitory
and studio or near an exit that opens and closes
frequently.
The place where the pipe is installed is highly
humid due to the lack of ventilation system.
Step 13 Checking the earthing
If the power distribution circuit does not have a earthing
or the earthing does not comply with specifications, an
earthing electrode must be installed. The corresponding
accessories are not supplied with the air conditioner.
1 Select an earthing electrode that complies with the
specifications given in the illustration.
2 Connect the flexible hose to the flexible hose port.
In damp hard soil rather than loose sandy or
gravel soil that has a higher earthing resistance.
Away from underground structures or facilities,
such as gas pipes, water pipes, telephone lines
and underground cables.
At least 6.6 ft away from a lightening conductor
earthing electrode and its cable.
NOTE
The earthing wire for the telephone line cannot be
used to ground the air conditioner.
Carbon plastic
19.69inch(50cm)
PVC-insulated
green/yellow
wire
To grounding screw
Steel core
11.81inch
(30cm)
Terminal M4
3 Finish wrapping insulating tape around the rest of the
pipes leading to the outdoor unit.
4 Install a green/yellow color earthing wire:
If the earthing wire is too short, connect an
extension lead in a mechanical way and wrap it
with insulating tape (do not bury the connection).
Secure the earthing wire in position with staples.
NOTE
If the earthing electrode is installed in an area with
heavy traffic, its wire must be connected securely.
5 Carefully check the installation by measuring the
earthing resistance with a earth resistance tester. If
the resistance is above the required level, drive the
electrode deeper into the ground or increase the
number of earthing electrodes.
6 Connect the earthing wire to the electrical component
box inside of the outdoor unit.