Installing the wind baffle
Installing the wind baffle
Installing the wind baffle
If you operate the cooling operation of air conditioner in the condition where ambient temperature is lower than 23 °F
DB(Dry bulb), or the outdoor unit might be faced with strong wind directly, the wind baffle should be installed to prevent
the outdoor unit fan from operating in reverse way.
Wind baffle is not supplied with the product.
Make holes on both sides and attach the
wind baffle using screws.
Make holes on both sides and attach the
wind baffle using screws.
24.6 inch (624.9mm)
0.6 inch (15.3mm)
Partition
<Front View>
"A"
<Top Down View>
A” – Should be 7 7/8 inch or longer
CAUTION
When attaching the wind baffle using screws, be careful that the screws do not damage the partition and the heat
exchanger.
NOTE
Install outdoor units with the back surface facing wall side to eliminate the effects of external wind.