Samsung Electronics12-22
12-4 Main Part Inspection Method
Room Temperature Sensor
Room Fan Motor
Stepping Motor
Measure resistance with a tester
Normal At the normal temperature 37kΩ~ 8.3kΩ(-7˚C~+30˚C)
*Refer to Table 12-3-4.
Abnormal ∞, 0Ω
. . .
Open or Short
Measure the resistance between terminals of the connector (CN72) with a tester.
Normal At the normal temperature (10˚C ~ 30˚C)
Abnormal ∞, 0Ω
. . .
Open or Short
Measure the resistance between the red wire and each terminal wire with a tester.
Normal About 300Ω at the normal temperature (20˚C ~ 30˚C)
Abnormal ∞, 0Ω
. . .
Open or Short
Breakdown Inspection MethodPart
Compare terminal Resistance Remark
Yellow, Blue 404.4Ω ± 10% Main
Yellow, Red 340Ω ± 10% Sub