11
3-2-3 When the Outdoor Unit Does Not Operate. (Initial Diagnosis)
1) Checklist :
(1) Is input voltage normal?(the rating voltage ±10% range)
(2) Is the set temperature of the remote control higher than room temperature in COOL mode?
(3) Is the set temperature of the remote control lower than room temperature in HEAT mode?
(4) Is the POWER IN connector (terminal-tab) linked correctly?
(5) Is the outdoor unit properly connected with the TERMINAL BLOCK connector(5P)?
2) Troubleshooting procedure
After unplugging out the power cord should be
reconnected within five seconds.
Does the operating lamp blink
YES
YES
NO
NO
NO 1
YES 3
2
NO
YES
1 NO
2 NO
Outdoor unit is
out of order.
Power relay is
out of order
Power relay should be
replaced.
PCB should be
checked.
Microcomputer is
out of order.
PCB should be checked.
Room temperature sensor is
out of order
Check as in the procedure "No Power parts"
Refer to page 5-2.
YES 3
Is the room sensor normal register?
10°C 20°C 30°C
17.96k 12.09k 8.3k
Does the timer lamp blink during operation ?
Is the power relay RY71 operated by adjusting the room
temperature?
Is the rating voltage ±10% range applied relay between
Terminal Tap(TB71) and RY 71 terminal No. 3
Test rod location Normal
+ - Condition Voltage
IC1 Pin No.63 GND RY73 ON DC 4.8V
1- 5/14/01 7:00 PM Page 11

Other manuals for Samsung AS12A2VC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung AS12A2VC and is the answer not in the manual?

Samsung AS12A2VC Specifications

General IconGeneral
BrandSamsung
ModelAS12A2VC
CategoryAir Conditioner
LanguageEnglish

Related product manuals