4-1-8 Function comparison of wired remote controller vs wireless remote controller
4-1-9 Option and dip switch(SW2) setting of ass'y main in PCB
Samsung Electronics
4-5
Installation
DIP SWITCH
1
2
3
4
5
OPTION ITEM
VENTILATOR FAN
DRAIN PUMP
FLOAT SWITCH
FILTER CLEANING PERIOD
INDOOR FAN MOTOR SPEED
SW ON
Not installed
Installed
Installed
1000 Hr
NORMAL SPEED
SW OFF
Not installed
Installed
Not installed
2000 Hr
HIGH SPEED
DEFAULT
-
-
-
-
-
PART NAME
Operation ON/OFF
Wind flow setting
Wind volume setting
Group operation
Test operation
Operation mode setting
Reservation function
Timer cancel
Temperature setting
Filter reset
Centralized control display
Self-diagnosis among the
group control
Error display
Master/slave setting
WIRED REMOTE CONTROLLER
ON/OFF available
Up and down control available (Cassette model)
Breeze/Mild/Strong adjustment available
16 chamber group operation available
Test operation by test button
Settable of auto/cooling/
dehumidifying/blowing/heating
Start/stop/start-stop reservation available
Timer cancel button provided (Duct model)
Cooling : 18˚C ~ 30˚C
Heating : 16˚C ~ 30 ˚C settable
Filter reset button provided
Displayed as centralized control
To display while scanning the installed set
during reset
Displayed as 2 digit segment
Master/slave settable by PCB option switch
Wireless REMOTE CONTROLLER
ON/OFF available
Up and down control available (Cassette model)
Breeze/Mild/Strong adjustment available
16 chamber group function not available
Available by combination of button during the
power reset without test button
Settable of auto/cooling/
dehumidifying/blowing/heating
Start/stop/start-stop reservation available
No timer cancel button
Cooling : 18°C ~30°C
Heating : 16°C ~30°C settable
Filter reset button proviced
No function
No function
No function
No function
In case of control for the wired remote controller
and wireless remote controller installed
individually, almost similar functions are
performed, and in case of combined use of wired
and wireless remote controllers, Enalbe/Disable
can be set at the wired remote controller for the
wireless remote controller but the 16 chambers
operation can be done only from wired remote
controller.
Duct-ADH1800E-2-1 4/12/00 5:44 PM Page 4-5