● ADH3200E, DH32ZA1(A2)
● ADH4400G, DH44ZA1(ZA2)
Indoor Unit Outdoor Unit
*Allowable pipe length : Max. 30m
*Allowable drop distance : Max. 15m
Indoor Unit Outdoor Unit
*Allowable pipe length : Max. 50m
*Allowable drop distance : Max. 25m
*Amount of refilling per extension length of 1m;
When extending the pipe length by more than 5m, 55gr(55gr: Outdoor Unit is higher than Indoor Unit) of R-22
refrigerant should be refilled per extension length of 1m.