Additional refrigerant
H/P H/R
Ø12.70 (5 m)
Ø12.70 (5 m)
Ø12.70 (5 m)
Ø6.35 (5 m)
Ø6.35 (10 m)
Ø6.35 (15 m)
Ø9.52 (10 m)
Ø9.52 (10 m)
Ø9.52 (10 m)
Ø9.52 (10 m)
Ø6.35 (5 m)
Ø9.52 (10 m)
46.4kW
4.5kW
5.6kW
5.6kW
7.1kW
7.1kW
7.1kW
7.1kW
3.6kW
Ø9.52 (1 m)
Ø12.70 (5 m)
Ø15.88 (10 m)
Ø12.70 (10 m)
Ø9.52 (15 m)
Ø9.52 (10 m)
Ø12.70 (10 m)
Ø9.52 (18 m)
Ø9.52 (18 m)
Ø9.52
(25 m)
Ø9.52
(15 m)
Ø9.52
(10 m)
MCU
MCU
Ø6.35 (2 m)
2.8kW
7.1kW
11.2kW
7.1kW
11.2kW
7.1kW
7.1kW
7.1kW
Ø6.35 (15 m)
61.6 kW (33.6 kW + 28.0 kW)
Refrigerant pipe installation
f Basic amount of refrigerant within the outdoor unit (kg)
- Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Classication AM080FXVAG AM100FXVAG AM120FXVAG AM140FXVAG AM160FXVAG
Basic type 5.5 5.2 5.5 7.7 7.4
Classication AM180FXVAG AM200FXVAG AM220FXVAG
AM240HXVAG AM260HXVAG
Basic type 8.7 8.4 8.4 14.3 14.3
Classication AM240MXVGNR AM260MXVGNR AM280MXVGNR
AM300MXVANR
Basic type 14.0 14.0 14.0 14.0
f Amount of additional refrigerant depending on the pipe size ()
- Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Size of liquid pipe Ø 6.35 Ø 9.52 Ø 12.70 Ø 15.88 Ø 19.05 Ø 22.22 Ø 25.40 Ø 28.58
Additional amount (kg/m) 0.02 0.06 0.125 0.18 0.27 0.35 0.53 0.65
- For the indoor unit already connected to EEV kit, the additional refrigerant charging is 0.01kg per meter regardless of
the pipe size.