INSTALLATION07
Connecting the assembly cable
Cable specication
Model
Power cable
(Outdoor Unit)
Interconnection cable
(Indoor-Outdoor)
Type GL
09/12
18/24
30
3G,1.0mm²,
H07RN-F(**09/12**)
3G,2.5mm²,
H07RN-F(**18/24**)
3G,4.0mm²,
H07RN-F(**30**)
Power Supply
3x1.0mm²,H07RN-F
(60245 IEC66)
10A(09/12)
20A(18/24)
25A(30)
F1/F2
communication
2x0.75mm²,H05RN-F
(60245 IEC57)
DRED Connected Wire -
4x0.75mm²,H05RN-F
(60245 IEC57)
(Only for reference)
-
Connecting the cable
Electrical work
(1) For electrical and earth works, comply with the ‘technical standards of electrical installations’ and the the ‘wiring
regulations of the Local wiring regulations.
(2)Tightentheterminalblockscrewto1.2~1.8N•m(12~18kgf•cm).
(3) Precautions when connecting terminal blocks of the indoor unit
Before connecting, make sure the connecting part of the terminal socket is facing upwards.
Upside down
The terminal
socketis damaged.
There is no ring
terminalto cover the wire.
There must be no space between the terminal and the screw when connected.
-Anyremainingspacemaybecomearehazardduetooverheatingoftheelectricalcontact.
The terminal socket
is upside down.
Either the screw is not fitted
properly or there is a space between
the screw and the ring terminal.
• Fortheterminalblockwiring,useawirewitharingterminalsocketonly.
Regular wires without a ring terminal socket may become a re hazard due to overheating of the electrical
contact during a wiring work.
• Connectthepowercabletotheauxiliarycircuitbreaker.Ifeverypolefailstoconnecttothepowersupply,
it must be incorporated in a wire with a contact opening of ≥3 mm.
• Useshieldcable(Category5;lessthan50pF/m)fornoisyenvironmentalsite.
• Powersupplycordsofpartsofappliancesforoutdooruseshallnotbelighterthanpolychloroprene
sheathed exible cord.
(CodedesignationIEC:60245IEC66/CENELEC:H07RN-F,IEC:60245IEC57/CENELEC:H05RN-F)