EasyManuals Logo

S&C PMH Series User Manual

S&C PMH Series
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
S&C Instruction Sheet 662-510 31
Appendix D
Table 7. Current-Limiting Fuses—Types Accommodated and S&C Holders Required
For use in PMH
Models
Rated, kV
Current-Limiting Fuse
S&C Holder
Manufacturer Type
Rating
Catalog Number
Max, kV Max Amperes, RMS
14.4
Kearney
B 8.3 30—112 3142-A1
Q
8.3
8.3
15.5
15.5
15.5
6—30
40—100
6—30
40—50
65—100
3142-A3
3142-A1
3142-A2
3142-A1
3142
Cooper Power Systems
McGraw-Edison NX®
8.3
8.3
15.5
15.5
1.5C—40C
50C—100C
1.5C—40C
50C—100C
3142-A3
3142-A1
3142-A2
3142
RTE® ELX
8.3
15.5
3—50
3—50
3142-A3
3142-A2
Westinghouse CX
8.3
15.5
3.5C—40C
4C—40C
3142-A3
3142-A2
Combined
Technologies, Inc.
X Limiter
8.3
8.3
15.5
15.5
12—40
50—140
12—40
50—100
3142-A3
3142-A1
3142-A2
3142
25
Kearney
B
15.5
22
30—100
25—65
3143R1-A1
3143R1-A1
Q
15.5
15.5
6—30
40—100
3143R1-A3
3143R1-A1
Cooper Power Systems
McGraw-Edison NX®
15.5
15.5
23
1.5C—40C
50C—100C
6C—40C
3143R1-A3
3143R1-A1
3143R1-A3
RTE® ELX
15.5
23
3—50
3—40
3143R1-A3
3143R1-A3
Westinghouse
CX 15.5 4C—40C 3143R1-A3
CXN 15.5 45C—60C 3143R1-A1
Combined
Technologies, Inc.
X Limiter
15.5
15.5
23
12—40
50—100
12—40
3143R1-A3
3143R1-A1
3143R1-A3
The single-barrel current-limiting fuses listed in this table are to be
purchased from the appropriate current-limiting fuse manufacturer.
The maximum voltage and maximum ampere ratings listed in this
table apply when the corresponding current-limiting fuse is used.
Con sult the appropriate current-limiting fuse manufacturer for complete
fuse ratings.
S&C Holders for use in 14.4-kV models of PMH Pad-Mounted Gear
are rated 14.4 kV nominal, 17.0 kV maximum, and 200 amperes maxi-
mum. S&C Holders for use in 25-kV models of PMH Pad-Mounted Gear
are rated 25 kV nominal, 29 kV maximum, and 200 amperes maximum.
Includes adapters when required.
Current-Limiting Fuses for Use in S&C PMH
Pad-Mounted Gear
Types Accommodated and Adapters Required
S&C Holders for current-limiting fuses are designed for use
in pad-mounted gear models that include mountings for
Fault Fiter Electronic Power Fuses. In PMH Pad-Mounted
Gear, these holders will accommodate the single-barrel
current-limiting fuses listed in Table 7 when the fuses
are equipped with -inch (16-mm) diameter mounting
studs at both ends. Depending on the length and diameter
of the current-limiting fuse to be used, adapters may be
required in order to t the fuse in the holder. Adapters,
when required, are furnished with the S&C Holder and are
signied by a sufx to the catalog number of the holder.
For instructions on installing current-limit ing fuses in S&C
Holders, refer to S&C Instruction Sheet 660-500.