9-2. Checking the Outdoor System
9-2-1. Checking the outdoor unit
Apply 220 V AC between terminals 1 and 2 on the
outdoor unit 3P terminal block.
Of the connector T-RUN/TEST terminals, short-circuit
the T-RUN terminal to the COM terminal.
NOTE: If the above check items are okay, but the outdoor unit does not operate, there may be a faulty connection between
the indoor unit and the outdoor unit.
ControlNo.
1
2
The LED (red) on the control circuit board must
illuminate.
The compressor and fan motor must turn ON.
(They turn ON a few seconds after the power is turned
ON.)
Check items (unit operation)