Outdoor Unit
B - 8
SGP-E190J2GU2
Model
SGP-E190J2GU2W
980(SGP-E190J2GU2)
990(SGP-E190J2GU2W)
External dimensions (mm)
Hei ght
2,253
W idth
1,735
Dept h
1,000(+106)
Weight (kg)
Performance (kW)
Cooling capacity
56.0
Heating capacity
67.0
Heating capacity
(low temperature)
67.0
Water heating
capacity(Cooling only)
22.5
Power supply
220 ~ 240V
Electrical characteristics 50Hz
Operating
current(A)
5.2
Power consumption
(kW)
1.07
Cooling
(230V)
Power factor (%)
94
Operating
current(A)
5.4
Power consumption
(kW)
1.15
Heating
(230V)
Power factor (%)
94
Start up current (A)
30
Fuel consumption (kW) G/C
Cooling
43.5/53.0
Heating
(standard)
46.0/54.3
Heating
(low temperature)
54.2/65.0
Compressor
Cooling oil volume (L)
4.1(HP-9)
Crank case heater (W)
30
Engine
Displacement(L) 2.472
Rated output(kW)
15.0
Type
Sanyo Genuine AP D-125
Lubricating oil
Quantity
(L)
50
Starter motor
DC12V×2.2kW
Starter type
AC/DC conversion type
DC starter
Engine cooling water
Quantity(L)
27
Concentration, freezing
temperature
50V/V%, -35
ºC
Cooling water pump rated
output(W)
Quantity(L)
Refrigerant×Quantity(kg)
HFC[R407C]×17
Air intake
Front and rear
Air outlet
Top
Piping
Refrigerant gas tube
38.1(brazed)
Refrigerant liquid tube
19.05(brazed)
Fuel gas port
R3/4(male screw)
Hot water intake port
Rp 3/4(famale screw)
Exhaust gas drain port
diameter(mm)
27 rubber hose
Operating noise dB(A)
58
Blower
Blower type
Propeller fan×2
Rated air volume (m
3
/min)
300
Rated output (kW)
0.45
Heater for drain filter (W)
60
Heater for cooling water
Cooling water heater(W)
250
Paint color (Munsell code)
Silky shade (1Y8.5/0.5)
Heating(low temperature)
Less than 20ºCDB, 15ºCWB27ºCDB, 19ºCWB 20ºCDB
2ºCDB, 1ºCWB7ºCDB, 1ºCWB35ºCDB
Operating condition Cooling Heating(standard)
Indoor air intake temperature
Outdoor air intake temperature
2. The value of cooling power consumption indicates the electrical power consumed during cooling overload operation when Indoor air intake
temperature is 32ºCDB/23ºCWB, and Outdoor air intake temperature is 43ºCDB.
3. The operating noise was measured at the position of 1.5 meter from the ground and 1 meter from the front of the unit. However, in an actual
installation there are various additional conditions, and normally the noise level is higher than the indicated value.
4. Under fuel consumption, G indicates 100% propane, with a calorific value of 37.78MJ/NM
3
+5%, and C indicates other gas.
5. The values shown in the table are for 50Hz.
6. The specification is subject to change without notice, due to improvements etc.
Notes
1. The cooling capacity and heating capacity described in the tables are the values when the unit operates under the test condition of JIS B 8627
2. Specification