1
1-347
Reference diagram for snow-proof vents – 1
Space requirements for setting – (1)
The models of SPW-C256 / 366VH8 with STK-BDRE80A
[Obstacle to the rear of unit] [Obstacle to the rear of unit]
Top is open:
(1) Single-unit installation (2) Obstacles on both sides
z
Top is open:
(1) Single-unit installation
z
Top is blocked by an obstacle:
z
Top is blocked by an obstacle:
z
Outdoor unit
ABCDEFG
SPW-C256 / 366VH8
150 150 300 200 300 150 200
Outdoor unit
HIJ
SPW-C256 / 366VH8
500 300 1000
Outdoor unit
MN
SPW-C256 / 366VH8
1000 1000
Outdoor unit
KL
SPW-C256 / 366VH8
500 150
In cases 2 and 3 the height of the obstacle
must be no taller than the height of the outdoor
unit.
Notes:
Unit: mm
Min. B
Min. C
Min. A
Min. D
Min. E
Min. G
Min. K
Min. L
Min. H
Min. I Min. I
Min. J
Min. M
Min. N
Min. E Min. E
Min. E
(2) Multiple-unit installation (2 or more units)
(3) Multiple-unit installation (2 or more units)
SM830160-03ClassicPAC-iA4.ind347347SM830160-03ClassicPAC-iA4.ind347347 2010/02/1610:26:552010/02/1610:26:55