EasyManua.ls Logo

Sanyo SPW-C366VH - Page 354

Sanyo SPW-C366VH
517 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1
1-348
0
Q
Q
Reference diagram for snow-proof vents – 2
Space requirements for setting – (2)
The models of SPW-C256 / 366VH8 with STK-BDRE80A
[Obstacle to the front and rear of unit]
The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must
be no taller than the height of the outdoor unit.
z
(1) Single-unit installation
(2) Obstacles on both sides
[Installation in front-rear rows]
The top and both sides must remain open. Either the obstacle to the front or the obstacle to the
rear must be no taller than the height of the outdoor unit.
z
Min. 1000
Min. P
or more
Min. O
or more
Min. 300 Min. 300
Min. 1000
Min. 300
Dimension Q
If a snow protection duct is attached after the unit is
installed, verify that dimension Q is 500 mm or more.
Outdoor unit
OP
SPW-C256 / 366VH8
1000 150
Min. 300
Min. 1500
Min. 2000
Min. 200
Dimension Q
If a snow protection duct
is attached after the unit is
installed, verify that dimension
Q is 500 mm or more.
SM830160-03ClassicPAC-iA4.ind348348SM830160-03ClassicPAC-iA4.ind348348 2010/02/1610:26:552010/02/1610:26:55

Table of Contents

Related product manuals