ECO MULTI SYSTEM Unit Specifications
SM830052
I-72
1
6. Ceiling Mounted Type
Indoor unit (C)
MODEL No. SPW-T363GH56
Source 220 - 230 - 240 V / 1 phase / 50 Hz
Controller P.C.B. Ass’y CR-X253GH (Microprocessor)
Fan (Number…diameter) mm Centrifugal (4 … ø 150)
Fan motor
Model…Nominal output W KFG4Q-101D5P…100 W
Source 220 - 230 - 240 V / 1 phase / 50 Hz
No. of pole…r.p.m. (230 V, High) rpm. 4…1,194
Coil resistance Ω BRN – WHT : 43.3 ORG – YEL : 349.3
(Ambient temperature 20 °C) WHT – VLT : 16.6 VLT – PNK : 40.8
VLT – ORG : 24.5
Safety device
Operating temperature Open °C 130 ± 5 °C
Close °C Differential 15 deg. (min.)
Run capacitor VAC, µF 440 V, 4.0 µF
Electronic refrigerating control valve
Solenoid control model EKV - MOZS559E0
Coil resistance (at 20 °C) Ω ORG – GRY : 46 , YEL – GRY : 46
RED – GRY : 46 , BLK – GRY : 46
Solenoid control valve model HKV - 30D16
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows…fin pitch mm 3 … 1.7
Face area m
2
0.34
Auto louver motor MC8 D
Auto louver motor…Rated V, Hz, W, rpm. 220 – 240 VAC, 50 Hz, 3 W, 3.3 rpm., 8 P
Coil resistance (at 25 °C) Ω 14,900 Ω ± 8 %
Dew proof heater V, W 240 V, 17 W