SM830052
I-73
ECO MULTI SYSTEM Unit Specifications
1
6. Ceiling Mounted Type
Indoor unit (D)
MODEL No. SPW-T483GH56
Source 220 - 230 - 240 V / 1 phase / 50Hz
Controller P.C.B. Ass’y CR-X253GH (Microprocessor)
Fan (Number…diameter) mm Centrifugal (4…ø150)
Fan motor
Model…Nominal output W KFG4Q-101D5P…100 W
Source 220 - 230 - 240 V / 1 phase / 50 Hz
No. of pole…r.p.m. (230 V, High) rpm. 4…1,212
Coil resistance BRN WHT : 43.3 ORG YEL : 349.3
(Ambient temperature 20°C) WHT VLT : 16.6 VLT PNK : 40.8
VLT ORG : 24.5
Safety device
Operating temperature Open °C 130 ± 5°C
Close °C Differential 15 deg. (min.)
Run capacitor VAC, µF 440 V, 4.5 µF
Electronic refrigerating control valve
Solenoid control model EKV - MOZS559E0
Coil resistance (at 20°C) ORG GRY : 46 , YEL GRY : 46
RED GRY : 46 , BLK GRY : 46
Solenoid control valve model HKV - 30D16
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows…fin pitch mm 3…1.7
Face area m
2
0.34
Auto louver motor MC8 D
Auto louver motor…Rated V, Hz, W, rpm. 220 240 VAC, 50Hz, 3 W, 3.3 rpm. 8 P
Coil resistance (at 25°C) 14,900 ± 8 %
Dew proof heater V, W 240 V, 17 W