SM830076
1. Specifications
1-3 Other Component Specifications
(A) Indoor Unit
MODEL No. XHS2432
Power Transformer ATR – II174B
Rated Primary 220 VAC, 60 Hz
Secondary 14.8 VAC 0.55 mA, 14.8 VAC 0.6 mA
Capacity
Coil resistance
WHT - WHT : 101 , BRN - BRN : 0.42
(Ambient temprature 77 °F)
Thermistor cut off temperature °F277
Thermistor (Coil sensor) : TH2, 3 PBC - 41E - S26
Coil resistance k 14 °F : 23.7 , 41 °F : 12.1
23 °F : 18.8 , 50 °F : 9.7
32 °F : 15.0 , 59 °F : 8.0
Thermistor (Room sensor) : TH1 KTEC - 35 - S6
Coil resistance k 32 °F : 16.5 , 104 °F : 2.7
41 °F : 12.8 , 113 °F : 2.2
50 °F : 10.0 , 122 °F : 1.8
68 °F : 6.3 , 131 °F : 1.5
86 °F : 4.0 ,
Drain pump WP20SL - 21
Rated 230 / 208 VAC, 12.5 W
Float switch FS - 0218 - 102
MAX Rated (Contact rated) 50 W, DC 5V, 0.1 mA
Solenoid control valve or coil
Solenoid control valve IKV - 24D12
Solenoid coil DKV - MOZS582E0
Indicator Lamp Ass'y IND - 3THS
Synchronized Motor MT8 - 3C