EasyManuals Logo

Satec Expertmeter Series Reference Guide

Satec Expertmeter Series
340 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
12
Volts reading = (27245 0)
(17,280 - 0)/(32767 0) + 0 = 14,368V
2. Current readings
Assume device settings: CT primary current = 200A.
Current engineering scales (see Section 4):
ENG_HI = Imax = CT primary current
2 = 200.00
2 = 400.00A
ENG_LO = 0A
If the raw data reading is 819 then the current reading in engineering units will be as follows:
Amps reading = (819 0)
(400.00 - 0)/(32767 - 0) + 0 = 10.00A
3. Power readings
a) Assume device settings (direct wiring): Wiring 4LL3; PT = 1; CT primary current = 200A; Voltage
scale = 828V.
Active Power engineering scales (see Section 4):
ENG_HI = Pmax = Vmax
Imax
2 = (828.0
1)
(200.00
2)
2 = 662,400W = 662.400kW
ENG_LO = -Pmax = -662.400kW
If the raw data reading is 18024 then the power reading in engineering units will be as follows:
Watts reading = (18024 - (-32768))
(662.400 - (-662.400))/(32767 (-32768)) +
(-662.400) = 364.368kW
If the raw data reading is -500 then the power reading in engineering units will be as follows:
Watts reading = (-500 - (-32768))
(662.400 - (-662.400))/(32767 (-32768)) + (-662.400) =
-10.097kW
b) Assume device settings (wiring via PT): Wiring 4LN3; PT = 120; CT primary current = 200A;
Voltage scale = 144V.
Active Power engineering scales (see Section 4):
ENG_HI = Pmax = Vmax
Imax
3 = (144
120)
(200.00
2)
3/1000 = 20,736kW
ENG_LO = -Pmax = -20,736kW
If the raw data reading is 12000 then the power reading in engineering units will be as follows:
Watts reading = (12000 - (-32768))
(20,736 - (-20,736))/(32767 (-32768)) +
(-20,736) = 7,594kW
If the raw data reading is -5000 then the power reading in engineering units will be as follows:
Watts reading = (-5000 - (-32768))
(20,736 - (-20,736))/(32767 (-32768)) +
(-20,736) = -3,164kW
4. Power Factor readings
Power factor engineering scales (see Section 4):
ENG_HI = 1.000.
ENG_LO = -1.000.
If the raw data reading is 29166 then the power factor in engineering units will be as follows:
Power factor reading = (29166 - (-32768))
(1.000 - (-1.000))/(32767 (-32768)) +
(-1.000) = 0.89

Other manuals for Satec Expertmeter Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Satec Expertmeter Series and is the answer not in the manual?

Satec Expertmeter Series Specifications

General IconGeneral
BrandSatec
ModelExpertmeter Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals