7 # 10 Failure Air pressure failure
No Symptoms and Causes Solutions Reference
The KDB-GOM boiler air pressure switch
always operates at the ON position of
contact B and displays failure code # 10
in case of back pressure or back fire.
1 The diaphragm inside the air pressure
switch is defective and the contact is OFF.
- Check the resistance of the air pressure switch
terminal when the boiler is idle and if it shows
an infinite level (ā€œ0ā€ is normal), it is defective
and the air pressure switch has to be
replaced.
<Fig. 1>
2 The installation and the position of the flue
is not appropriate.
- Correct the flue due the formation of a wind
pressure zone.
- Check whether the connector terminal is well
assembled and reconnect.
If the symptoms remain after checking the
above, replace the main controller.
<Fig. 1>