KDB-GOM
Series
- 54 -
Switch DIP switch #5 (“B”) on the main controller to the new settings
Table 2
.
L.P. Gas
: DIP switch # 5 "ON"
Natural Gas : DIP switch # 5 "OFF"
[Fig. 1] Procedure of gas conversion
[Table 2] DIP switch setting on the main controller
[Table 3] Gas modulating valve head(
H
2
O)
No ON OFF
1
Trial operation Normal
2
Forced Max. Combustion Normal
3
Forced Min. Combustion Normal
4
F. E F. F
5
L.P Gas Natural Gas
6
Sealed combustion Open Combustion
7
50 Hz 60 Hz
Gas Modulating head Pressure , mmH
O(inch W.C.)
Max. Load Min. Load
Front Panel
ON
Front Panel
OFF
Front Panel
ON
Front Panel
OFF
KDB-161GOM-NG Natural Gas 100 (3.94) 104 (4.10) 16 (0.63) 18 (0.71)
φ
1.33 (0.052)
161GOM-LP L.P. Gas 170 (6.70) 174 (6.86) 26 (1.02) 28 (1.10)
φ
0.92 (0.036)
KDB-201GOM-NG Natural Gas 104 (4.10) 108 (4.26) 16 (0.63) 18 (0.71)
φ
1.46 (0.057)
201GOM-LP L.P. Gas 150 (5.91) 154 (6.07) 26 (1.02) 28 (1.10)
φ
1.06 (0.041)
KDB-251GOM-NG Natural Gas 104 (4.10) 110 (4.34) 20 (0.79) 22 (0.87)
φ
1.37 (0.053)
251GOM-LP L.P. Gas 164 (6.46) 170 (6.70) 24 (0.95) 26 (1.02)
φ
0.95 (0.037)
KDB-301GOM-NG Natural Gas 106 (4.18) 116 (4.57) 20 (0.79) 22 (0.87)
φ
1.50 (0.059)
301GOM-LP L.P. Gas 156 (6.15) 166 (6.54) 28 (1.10) 30 (1.18)
φ
1.06 (0.041)
- Key -
Igniter wire & Ignition sensor
Ignition Transformer
Combustion chamber Nozzle Assembly
STEP 3.
STEP 3.STEP 3.
STEP 3.